Jira-REVIT-210122 #122

Closed
MatthewSteen opened this issue Jul 26, 2023 · 1 comment · Fixed by #123 or #135
Closed

Jira-REVIT-210122 #122

MatthewSteen opened this issue Jul 26, 2023 · 1 comment · Fixed by #123 or #135
Assignees
Labels
bug Something isn't working

Comments

@MatthewSteen
Copy link
Member

See https://jira.autodesk.com/browse/REVIT-210122.

** Severe ** AirConditioner:VariableRefrigerantFlow = WC VRF
** ~~~ ** Condenser Type = WATERCOOLED
** ~~~ ** Illegal Heating Performance Curve Outdoor Temperature Type input for this object = WETBULBTEMPERATURE
** ~~~ ** ... input must be DRYBULBTEMPERATURE when Condenser Type is WaterCooled.
** ~~~ ** ... Heating Performance Curve Outdoor Temperature Type will be reset to DRYBULBTEMPERATURE and simulation continues.
** Fatal ** GetVRFInput: Errors found in getting AirConditioner:VariableRefrigerantFlow system input. Preceding condition(s) causes termination.

@MatthewSteen
Copy link
Member Author

** Warning ** GetVRFInput: AirConditioner:VariableRefrigerantFlow="AC VRF" curve values
** ~~~ ** ... Cooling Capacity Ratio Modifier Function of Low Temperature Curve Name = AIR CONDITIONER VARIABLE REFRIGERANT FLOW 1 VRFCOOLCAPFT output is not equal to 1.0 (+ or - 10%) at rated conditions.
** ~~~ ** ... Curve output at rated conditions = 1.136
** Warning ** GetVRFInput: AirConditioner:VariableRefrigerantFlow="AC VRF", invalid
** ~~~ ** ...Cooling Energy Input Ratio Modifier Function of Low Part-Load Ratio Curve Name = AIR CONDITIONER VARIABLE REFRIGERANT FLOW 1 COOLINGEIRLOWPLR has out of range value.
** ~~~ ** ...Curve minimum value of X = 0.500 must be <= Minimum Heat Pump Part-Load Ratio = 0.250.
** Warning ** GetVRFInput: AirConditioner:VariableRefrigerantFlow="AC VRF", invalid
** ~~~ ** ...Heating Energy Input Ratio Modifier Function of Low Part-Load Ratio Curve Name = AIR CONDITIONER VARIABLE REFRIGERANT FLOW 1 HEATINGEIRLOWPLR has out of range value.
** ~~~ ** ...Curve minimum value of X = 0.500 must be <= Minimum Heat Pump Part-Load Ratio = 0.250.
** Warning ** GetVRFInput: AirConditioner:VariableRefrigerantFlow="WC VRF", invalid
** ~~~ ** ...Cooling Energy Input Ratio Modifier Function of Low Part-Load Ratio Curve Name = AIR CONDITIONER VARIABLE REFRIGERANT FLOW 1 COOLINGEIRLOWPLR 1 has out of range value.
** ~~~ ** ...Curve minimum value of X = 0.500 must be <= Minimum Heat Pump Part-Load Ratio = 0.250.
** Warning ** GetVRFInput: AirConditioner:VariableRefrigerantFlow="WC VRF", invalid
** ~~~ ** ...Heating Energy Input Ratio Modifier Function of Low Part-Load Ratio Curve Name = AIR CONDITIONER VARIABLE REFRIGERANT FLOW 1 HEATINGEIRLOWPLR 1 has out of range value.
** ~~~ ** ...Curve minimum value of X = 0.500 must be <= Minimum Heat Pump Part-Load Ratio = 0.250.
** Fatal ** GetVRFInput: Errors found in getting AirConditioner:VariableRefrigerantFlow system input. Preceding condition(s) causes termination.